PM Guide # Item LOCATION Quantity
A-01A Air Dryer, RM 128A Boiler Mechanical Room 1
A-04A Air Compressor, RM 128 Chiller Mechanical Room 1
A-04A Air Compressor, RM 128 Chiller Mechanical Room 1
A-09B Air Cooled Condenser Roof 1
A-09B Air Cooled Condenser Roof 1
A-11A AHU #1, 5000 CFM, Chiller RM Chiller Mechanical Room 1
A-11A AHU #2, 5000 CFM, Chiller RM Chiller Mechanical Room 1
A-11A AHU #4, 5000 CFM, Penthouse Penthouse Mechanical Room 1
A-11A AHU #5, 5000 CFM, Penthouse Penthouse Mechanical Room 1
A-11B AHU #3, 15000 CFM, Penthouse Penthouse Mechanical Room 1
B-02B HW Boiler #1, Gas, RM 128A Boiler Mechanical Room 1
B-02B HW Boiler #2, Gas, RM 128A Boiler Mechanical Room 1
B-03A Burner #1, Gas, RM 128A Boiler Mechanical Room 1
B-03A Burner #2, Gas, RM 128A Boiler Mechanical Room 1
C-02A Remote Air Intake Damper, 28" x 30", AHU #1 Boiler Mechanical Room 1
C-02A Remote Air Intake Damper, 24" x 24", AHU #2 Boiler Mechanical Room 1
C-02A Remote Air Intake Damper, 28" x 30", AHU #4 Penthouse Mechanical Room 1
C-02A Remote Air Intake Damper, 24" x 24", AHU #5 Penthouse Mechanical Room 1
C-02A Remote Air Intake Damper, 36" x 96", AHU #3 Penthouse Mechanical Room 1
C-03A Coils, Preheat, 22" x 34" Chiller Mechanical Room 1
C-03A Coils, Preheat, 22" x 34" Chiller Mechanical Room 1
C-03A Coils, Preheat, 22" x 34" Penthouse Mechanical Room 1
C-03A Coils, Preheat, 22" x 34" Penthouse Mechanical Room 1
C-03A Coils, Preheat, 22" x 34" Penthouse Mechanical Room 1
C-04A Central Mini Computer, HVAC, Powers, RM 112 1 Floor 1
C-04A MBU, HVAC, Powers, 32 Control Points Chiller Mechanical Room 1
C-04A MBU, HVAC, Powers, 64 Control Points Penthouse Mechanical Room 1
C-05A Automatic Mixing Box, Pneumatic Chiller Mechanical Room 5
C-06A Controls, HVAC, Sensors, RM 128 Chiller Mechanical Room 6
C-06A Controls, HVAC, Sensors, Penthouse Penthouse Mechanical Room 11
C-06A Controls, Room Sensors, 1st Floor 1 Floor 5
C-06A Controls, Room Sensors, 2nd Floor 2 Floor 10
C-06A Controls, Room Sensors, 3rd Floor 3 Floor 10
D-03B Drains, Bucket Type Roof 9
D-04A Door, Hydraulic, Entrance 1 Floor 2
D-05A Door, Main Entrance 1 Floor 4
D-10A Door, Overhead, Manual 9' x 10' 1 Floor 1
E-17A Expansion Joints Chiller Mechanical Room 2
E-18A Emergency Lights 1 Floor 4
E-18A Emergency Lights 2 Floor 4
E-18A Emergency Lights 3 Floor 8
E-18A Emergency Lights Penthouse Mechanical Room 1
E-26A LV Power Circuit Breaker, 600 AMP, 600V, Type K1600 Chiller Mechanical Room 1
E-27A LV Power Circuit Breaker, 1600 AMP, 600V, Type K1600 Chiller Mechanical Room 1
E-30A Switchboard, 1200 AMP, 208V, 12 Cubicles Chiller Mechanical Room 1
E-34A Disconnect, LV, 400 AMP, 240V Chiller Mechanical Room 1
E-34A Disconnect, LV, 400 AMP, 240V Chiller Mechanical Room 1
E-51A Motor Starter, 15 HP CW Pump Chiller Mechanical Room 1
E-51A Motor Starter, 15 HP CW Pump Chiller Mechanical Room 1
F-11A Fire Doors 1 Floor 4
F-11A Fire Doors 2 Floor 2
F-11A Fire Doors 3 Floor 2
F-11A Fire Doors Penthouse Mechanical Room 1
F-14A Automatic Smoke Detector Chiller Mechanical Room 2
F-14A Automatic Smoke Detector Penthouse Mechanical Room 3
F-15A Fire Alarm Panel 1 Floor 1
F-17A Fire Alarm Pull Box, 1st Floor 1 Floor 3
F-17A Fire Alarm Pull Box, 2nd Floor 2 Floor 3
F-17A Fire Alarm Pull Box, 3rd Floor 3 Floor 1
F-17A Fire Alarm Pull Box, Penthouse Penthouse Mechanical Room 1
F-18A Fire Dampers, 22" x 22" Chiller Mechanical Room 1
F-18A Fire Dampers, 22" x 22" Chiller Mechanical Room 1
F-20A Sprinkler Heads, 418 SF Throughout Entire Building 1
F-24A Fire Extinguishers, Stored Pressure w/gauge, Non-Stainless 1 Floor 6
F-24A Fire extinguishers, Stored Pressure w/gauge, Non-Stainless 2 Floor 6
F-24A Fire extinguishers, Stored Pressure w/gauge, Non-Stainless 3 Floor 6
F-27A Fan Centrifugal #1, 800 CFM, 3/4 HP 3 Floor 1
F-27A Fan Centrifugal #2, 1000 CFM, 3/4 HP Boiler Mechanical Room 1
F-27A Fan Centrifugal #3, 5000 CFM, 2 HP Penthouse Mechanical Room 1
F-27A Fan Centrifugal #4, 1000 CFM, 1 HP Penthouse Mechanical Room 1
F-27A Fan Centrifugal $5, 1500 CFM, 3/4 HP Penthouse Mechanical Room 1
F-32A Filter, Throw Away, 20 x 25 x 2, AHU #1, RM B-128 Chiller Mechanical Room 6
F-32A Filter, Throw Away, 24 x 24 x 2, AHU #2, RM B-128 Chiller Mechanical Room 4
F-32A Filter, Throw Away, 20 x 25 x 2, AHU #3, Penthouse Penthouse Mechanical Room 12
F-32A Filter, Throw Away, 16 x 20 x 2, AHU #4, Penthouse Penthouse Mechanical Room 8
F-32A Filter, Throw Away, 16 x 20 x 2, AHU #5, Penthouse Penthouse Mechanical Room 4
F-34H Fluorescent Light Fixtures, Louver, 2-Lamp, 48", Halls & Stairwells 1 Floor 16
F-34H Fluorescent Light Fixtures, Louver, 2-Lamp, 48", Halls & Stairwells 2 Floor 16
F-34H Fluorescent Light Fixtures, Louver, 2-Lamp, 48", Halls & Stairwells 3 Floor 16
F-34J Fluorescent Light Fixtures, Louver, 4-Lamp, 48" 1 Floor 16
F-34J Fluorescent Light Fixtures, Louver, 4-Lamp, 48" 2 Floor 16
F-34J Fluorescent Light Fixtures, Louver, 4-Lamp, 48" 3 Floor 16
F-36A Fan Propeller, 24", 3/4 HP Boiler Mechanical Room 1
H-02A Hot Water Heater, 120 Gal, Cyclone, RM 128A Boiler Mechanical Room 1
I-02A Fan Coil Unit, Under Window, Front Entrance 1 Floor 1
L-04B Outside Lighting Outside 60
L-05A Lawn Sprinklers Outside 18
M-02A Man Hole Cover Outside 1
M-03A Motor, Radiator HW Pump, RM 128A Boiler Mechanical Room 1
M-03A Motor, AHU #1, RM 128, A-11A-001 Chiller Mechanical Room 1
M-03A Motor, AHU #2, RM 128, A-11A-002 Chiller Mechanical Room 1
M-03A Motor, AHU #4, Penthouse, A-11A-003 Penthouse Mechanical Room 1
M-03A Motor, AHU #5, Penthouse, A-11A-004 Penthouse Mechanical Room 1
M-03A Motor, Centrifugal Fan Penthouse Mechanical Room 1
M-03A Motor, 2 HP, Centrifugal Fan Penthouse Mechanical Room 1
M-03B Motor, 15 HP, AHU#3, Penthouse, A-11B-001 Penthouse Mechanical Room 1
M-03B Motor, 15 HP, Centrifugal Pump Chiller Mechanical Room 1
M-03B Motor, 15 HP, Centrifugal Pump Chiller Mechanical Room 1
P-03A Pump Centrifugal #1, Marathon, 15HP, CW & HW Pump Chiller Mechanical Room 1
P-03A Pump Centrifugal #2, Marathon, 15HP, CW & HW Pump Chiller Mechanical Room 1
P-03A Pump Centrifugal #3, Marathon, 2HP, Radiator Circulating Water Boiler Mechanical Room 1
R-01A Radiator #1, 1st FL NE Stairwell Stairwell #1 7
R-01A Radiator #2, 1st FL SE Stairwell Stairwell #2 1
R-01A Radiator #3, 2nd FL NE Stairwell Stairwell #1 1
R-01A Radiator #4, 2nd FL SE Stairwell Stairwell #2 1
R-01A Radiator #5, 3rd FL NE Stairwell Stairwell #1 1
R-01A Radiator #6, 3rd FL SE Stairwell Stairwell #2 1
R-02A Roof Inspection, 17,500 SQ FT Roof 175
R-06B Refrigeration Machine, York, 81 Ton with 2 Compressors, RM 128 Chiller Mechanical Room 1
R-06B Refrigeration Machine, York, 81 Ton with 2 Compressors, RM 128 Chiller Mechanical Room 1
R-08A Central Refrigeration Control Panel, 81 Ton, RM 128 Chiller Mechanical Room 1
R-08A Central Refrigeration Control Panel, 81 Ton, RM 128 Chiller Mechanical Room 1
R-11A Refrigeration Controls, Central System, RM 128 Chiller Mechanical Room 4
U-01A Unit Heater, Hot Water, Main Entrance 1 Floor 1
V-03A Valve, Regulating, 6", CHW & HW, RM 128 Chiller Mechanical Room 1
V-03A Valve, Regulating, 2", CHW & HW, Penthouse Penthouse Mechanical Room 2
V-03A Valve, Regulating, 2 1/2", CHW & HW, Penthouse Penthouse Mechanical Room 2
V-05A Valve, Critical, 6" CHW, RM 128 Chiller Mechanical Room 1
V-05A Valve, Critical, 5" CHW, RM 128 Chiller Mechanical Room 1
V-05A Valve, Critical, 4" CHW & HW, RM 128 Chiller Mechanical Room 9
V-05A Valve, Critical, 5" HW, RM 128A Boiler Mechanical Room 2
V-05B Valve, Critical, 4" HW, RM 128A Boiler Mechanical Room 4
V-05B Valve, Manual, 2" HW, RM 128A Boiler Mechanical Room 3
V-05B Valve, Manual, 2 1/2" CW & HW, Penthouse Penthouse Mechanical Room 4
V-05B Valve, Manual, 3" CW & HW, Penthouse Penthouse Mechanical Room 4
V-05B Valve, Manual, 2" CW & HW, Penthouse Penthouse Mechanical Room 4
V-09A Back Flow Preventer, 1 1/2", Boiler Room Boiler Mechanical Room 1
W-02A Emergency Eye Wash Station Chiller Mechanical Room 1
W-08A Water Treatment, Cold Water, Closed Loop, RM 128 Chiller Mechanical Room 1
W-09A Water Treatment, Hot Water, RM 128A Boiler Mechanical Room 1